        • Name: SF-104P

        Features 

        Temperature control

        Manual/automaticdefrost by electric heater

        Evap. Fan Control

        Value Storing

        Self  Testing /Parameter Locking


        Technical Data 
        Range of temperature displayed : 
        -45~150℃(-40~150℉)
        Range of set temperature: -45~45℃(-40~120℉)
        Accuracy:±1℃(±2℉)
        Compressor: N.O. 30A/250VAC
        Defrost: N.O. 10A/250VAC
        Evap. Fan: N.O. 5A/250VAC
        Dimension:77(Length)×35(Width)×70(Depth)mm
        Mounting hole dimension:71(Length)×29(Width)mm


        Parameters 

        Parameter

        Function

        Set range

        Default

        PA

        Password

        0099

         

        E1

        Lower setpoint limit

        -45℃/-45℉~Set temp.

        -22℃/-8℉

        E2

        Higher setpoint limit

        Set temp.~45℃/120℉

        10℃/50℉

        E3

        Temp.Hysteresis

        1~20℃/1~36℉

        5℃/9℉

        E4

        Comp.start delay time

        0~10Min

        2Min

        E5

        Offset on room temp.

        -20~20℃/℉

        0

        E6

        Offset on evap.temp.

        -20~20℃/℉

        0

        F1

        Max.defrost duration

        1~60Min

        20Min

        F2

        Defrost interval time

        0~24Hr

        4Hr

        F3

        Defrost termination temp.

        0~30℃/32~68℉

        12℃/54℉

        F4

        Display during defrost

        0=Normal display
        1=Last value before defrost

        1

        F5

        Fan operating function

        0=Parallel with comp.

        1 = Continuous running except defrost

        2= Evaporator temper-ature control

        0

        F6

        Dripping time

        0~10 Min

        2Min

        F7

        Fan delay start mode

        after defrost

        0=time

        1=Controlled by F9

        1

        F8

        Fan delay start time

         after defrost.

        0~10Min

        2

        F9

        Fan start temp.

        (Defrost sensor temp.)

        -30~30

        -22~86

        -4

         25

        C1

        Temperature unit

        Celsius=℃Fahr.=

        C2

        High temperature alarm

        Set value~49℃/121℉~OFF

        40

        104

        C3

        Low temperature alarm

        OFF~~44℃/44℉~Set value

        OFF

        C4

        Alarm time delay

        0~90Min

        30Min


         

        Download instructions: SF-104 【查看】