SF-385

Number of views:
0
Quantity
-
+
1
Description
"

Features
Mini-sized and integrated intelligent control .
Temperature Display / Temperature Control /
Value Storing /Parameter Locking/ Self Testing

Technical Data
Temperature sensor:  NTC two sensors, 2m(L) (Neither positive nor negative)
Range of temperature displayed:-45℃~120℃(-49~248℉);
Accuracy:±1℃(±2℉)
Range of set temperature:-45℃~45℃(-49~113℉);
Factory default: 00℃(32℉)
Relay output contact capacity:
Compressor : N. O. 30A/250VAC
Fan: N. O. 10A/250VAC
Defrost: N. O. 10A/250VAC

Paramete

Paramete Function Set range Default
E1 Lower set point limit
-45℃
-49℉  ~set temp
-35℃
-31℉
E2 Higher set point limit
45℃
~set temp 113℉
20℃
68℉
E3 Temp. Hysteresis
01~10℃
02~18℉
04℃
07℉
E4 Comp. start delay time 00~10 min 2 min
E5 Offset on room temp.
-20~20℃
-36~36℉
00℃
00℉
E6 Offset on evap. temp.
-20~20℃
-36~36℉
00℃
00℉
F0 Defrost  type
00=electric heat
01=hot gas
02=defrost by turning off 
00
F1 Defrost duration 01~90min 20 min
F2 Defrost interval 00~24hr 6 hr
F3
Defrost termination
temp.
00~20℃
32~68℉
08℃
46℉
F4
Display
during defrost
00=normal display
01=last value before defrost
02=display dEF
01
F5 Fan control
00=synchonized with comp.(stop when defrost)
01=keep working(stop when defrost)
02=synchronized with comp.(start when defrost)
03=keep working(start when defrost)
01
F6 Dripping time 00~30min 2 min
C1
Cold room high
temp. Alarm
C2~  45℃
113℉
45℃
113℉
C2
Cold room low
temp. Alarm
-45℃
-49℉  ~C1
-40℃
-40℉
C3 Alarm hysteresis
01~20℃
02~36℉
02℃
04℉
C4 Alarm delay time 00~90min 30 min
CF Temperature unit ℃=Celsius ℉=Fahrenheit
"