SF-373

Number of views:
0
Quantity
-
+
1
Description
"

Features
Mini sized and integrated intelligent temperature control.
Temperature Display / Temperature Control /
Value Storing/Self  Testing /Parameter Locking

Technical Data
Temperature sensor: NTC, one sensor, 2 meters long, neither positive nor negative
Range of temperature display:-45~120℃(-49~248℉)
Accuracy:±1℃ /±2℉
Range of set temperature:-45~45℃(-49~113℉)
Factory default : 04℃ /39℉
Dimension:150(Length)×93(Width)×45(Depth)mm
Mounting hole dimension:142.5(Length)×85.5(Width)mm
Relay output  contact capacity
Compressor:  N. O.  30A/250VAC
(applicable to one HP Compressor, if more it needs to connect an to AC contactor)
Evap. Fan: N. O.  10A/250VAC
Light: N. O.  10A/250VAC
Demist: N. O.  10A/250VAC

Paramete

Paramete Function Set range Default
E1 Lower set point limit
-49℉
-45℃~set temp.
-35℃
-31℉
E2 Higher set point limit
set temp.~113℉
           45℃
20℃
68℉
E3 Temp. hysteresis
01~10℃
02~18℉
04℃
07℉
E4 Comp. Start delay time 00~10min 2min
E5 Offset on room temp.
-20~20℃
-36~36℉
00℃
00℉
F1 Max. Defrost duration 01~90 min 20 min
F2 Defrost interval time 00~24hr 6hr
F4 Display during defrost
00=Normal display
01 = Last value before  defrost
02=display DEF
01
F5 Fan control
00=Parallel with comp.(stop when defrost)
01 = Continuous running 
   (stop when defrost)
02= Parallel with comp. (Start when defrost)
03=keep running(start when defrost)
03
C1 High temp. alarm
45℃
       113℉  ~C2
45℃
113℉
C2 Low temp.  alarm
-45℃
-49℉~C1
-40℃
-40℉
C3 Alarm hysteresis
01~20℃
02~36℉
02℃
04℉
C4 Alarm delay time 00~90min 30min
CF Temp. unit ℃=Celsius  ℉=Fahrenheit
"
We could not find any corresponding parameters, please add them to the properties table